INST.No.INE-868G [DB600] General Instruction Manual
- 149 -
7-6-4
Auto adjustment
(1) Initialization of setting value
Check that the parameters are set to ensure the output range of 0 to 100%
Make sure measured value (PV) does not become over-range.
Set "Output variation limiter for rise/fall (MODE6)" to -100.0%/100.0%.
Set "Output limiter lower limit/higher limit (MODE3)" to 0.0%/100.0%. To perform tuning within the
range of output limiter, set range of lower limit/higher limit to "60% or more".
Set "Motor·deadband (MODE6)" to 4.0% (default)
(2) Motor fully close fully open time adjustment
Select "" on operation screen "Motor tuning" and press [ENT] key to start motor tuning. At this
time, "O1" on the display light, and display switches from "" to " ", then the actuator
moves to CLOSE side.
Press [>] key after making sure that the actuator is fully close.
Next, "O2" on the display light, and display switches from " " to " ", then the actuator
moves to OPEN side.
Press [>] key after making sure that the actuator is fully open. By this operation, time of the actuator
fully open to fully close is calculated automatically.
*Measures motor working time from fully close to fully open. Operate to measure accurate time.
When the motor tuning ends, "Motor tuning" returns to "".
Automatically calculated time is registered to MODE6 "Motor fully close fully open time" automatically,
check the calculated time.
(3) Deadband adjustment
Change the instrument setting to manual output operation (manual output) and set output value to
50.0%
Gradually raise the set value of "Motor·deadband" on MODE6 to calculate deadband of open side
relay drive (O2 display) and close side relay drive (O1 display).
Perform test run and gradually raise deadband value in a range that does not effect controllability.
Finally decide the highest value that does not effect the use of the instrument as set value of
"Motor·deadband".
7-6-5
Manual adjustment
(1) Time registration
Set shifting time of the actuator fully close to fully open to MODE6 "Motor fully close fully open
time".
(2) Deadband adjustment
Change the instrument setting to manual output operation (manual output) and set output value
to 50.0%
Gradually raise the set value of "Motor·deadband" on MODE6 to calculate deadband of open
side relay drive (O2 display) and close side relay drive (O1 display).
Perform test run and gradually raise deadband value in a range that does not effect controllability.
Finally decide the highest value that does not effect the use of the instrument as set value of
"Motor·deadband".