INST.No.INE-868G [DB600] General Instruction Manual
- 119 -
6-2 Linear scale
The default values of measuring range and linear scale are set as follows for the linear input (mV, V).
Input type Scale range Measuring range (default) Linear scale range (default)
20mV -20.00 to 20.00mV 0.00 to 20.00mV 0.0 to 2000.0
100mV -100.0 to 100.0mV 0.0 to 100.0mV 0.0 to 2000.0
5V -5.000 to 5.000V 0.000 to 5.000V 0.0 to 2000.0
10V -10.000 to 10.000V 0.000 to 10.000V 0.0 to 2000.0
- Setting procedure -
(1)
Set the minimum and maximum values of the analog signal input from the sensor with
"Measuring range lower/higher limit (MODE5)".
(2) Check the control range (display range), and set the decimal point position and the scale
lower/higher limit with "Linear scale zero/span (MODE5)".
Example 1) Setting a control range of 0.00 to 100.00 for 0 to 20mV
Measuring range ·· Lower limit: 0.00, higher limit: 20.00
Linear scale ········· Decimal point: DOT2, zero: 0.00, span: 100.00
Example 2) Setting a control range of 0.00 to 100.00 for 4 to 20mA (250Ω/external)
Input type ············ ±5V
Measuring range ·· Lower limit: 1.000, higher limit: 5.000
Linear scale ········· Decimal point: DOT2, zero: 0.00, span: 100.00