INST.No.INE-868G [DB600] General Instruction Manual
- 41 -
⑦ Operating condition display
• Constant value operation (program operation OFF)
RUN RUN Lights while constant operation RUN.
STOP (Unused)
READY READY Lights while constant operation READY.
WAIT WAIT
Lights when alarm event is reset.
Lights when alarm event is waiting.
REM REMOTE
Lights on remote SV during operation.
(At digital remote, lights after receiving
remote SV from communication)
AT
Auto
Tuning
Lights while executing PID auto tuning.
Blinks while FB auto tuning
MAN MANUAL
Lights when manual output.
Blinks when preset manual output.
• Program operation (program operation ON) *with program
function specifications
RUN RUN
Lights while program operation RUN.
OFF when program operation is
RESET/ STOP/ END.
STOP STOP Lights while program operation STOP.
READY RESET Lights while program operation RESET.
WAIT WAIT
Lights when alarm event is reset.
Lights when alarm event is waiting.
REM (Unused)
AT
Auto
Tuning
Lights while executing PID auto tuning.
Blinks while FB auto tuning
MAN MANUAL
Lights when manual output.
Blinks when preset manual output.
⑧ Setting value ramp display
• Constant value operation (program operation OFF)
△
SV rise ramp
Lights SV rate of change rise is set
while SV is rise ramp.
▽
SV fall ramp
Lights SV rate of change fall is set
while SV is fall ramp.
• Program operation (program operation ON) *with program
function specifications
Lights (during STOP) /blinks (during
RUN) when Current step start SV <
Current step end SV
Lights (during STOP) /blinks (during
RUN) when Current step start SV =
Current step end SV
Lights (during STOP) /blinks (during
RUN) when Current step start SV >
Current step end SV
While program operation RESET/END
Lights when
Next step start SV > Next step end SV
Lights when
Next step start SV = Next step end SV
Lights when
Next step start SV < Next step end SV
While program operation RESET
Next step is step END/Pattern link
⑨ Pattern No. (program operation ON) *with program function
specifications
PTN1 Pattern No.1
Executing pattern No. lights while
displaying operation screen/ MODE0
executing SV and displaying executing
step time.
Currently setting pattern No. lights
while displaying MODE2.
Entire pattern No. lights on entire
pattern common setting screen.
PTN2 Pattern No.2
PTN3 Pattern No.3
PTN4 Pattern No.4
⑩ Execution No./ step No.
• Constant value operation (program operation OFF)
No.
Execution No.
Setting No. lights when selecting
execution No. for constant value
operation while displaying operation
screen/ MODE0 screen.
Group No.
While displaying MODE3 screen, group
No. is displayed.
Event No.
While displaying MODE4 screen, event
No. is displayed.
• Program operation (program operation ON) *with program
function specifications
STP Step No.
Lights while displaying operation screen.
Executing step No. is displayed while
displaying operation screen/ MODE0
executing SV and displaying executing
step time.
Currently setting step No. is displayed
while displaying MODE2.
While displaying operation screen and
executing guaranty soak, step No.
blinks.
No.
Execution No.
Lights while displaying setting screen of
MODE0.
・ Selected No. of execution No. for
program operation is displayed
・ While setting No.0, previously set last
execution No. except for No.0 is
displayed.
Group No.
While displaying MODE3 screen, group
No. is displayed.
Event No.
While displaying MODE4 screen, event
No. is displayed.
⑪ Operation screen display
SV PV/SV
Lights while displaying [PV/SV] of
operation screen.
OUT PV/OUT1
Lights while displaying [PV/OUT1] of
operation screen.
OUT2 PV/OUT2
Lights while displaying [PV/OUT2] of
operation screen.
*with output 2 specifications
⑫ Communication status display
*with communication interface specifications
• Communication display (MODEa) is ON
S SEND
Blinks while sending communication
command.
R RECEIVE
Blinks while receiving communication
command.
*Communication status of engineering port is not displayed.