INST.No.INE-868G [DB600] General Instruction Manual
- 84 -

□□□

SEL
SEL
PID
P (8 types) Sets the P constant for 8 types.
"
□□□

"
Two-position control
"
□□□

"
to
"

"
P constant (PID control)
0.1 to 999.9 [%]
Use the [
], [
] and [ENT] keys to set the P constant for 8 types.
Use the [>] key to move the cursor to the right digit.
Setting of
(proportional band) is % of measuring range (linear scale for linear
input).
Set the numbers for 8 types at "Group No. (MODE3)".

□□□

SEL
SEL
I (8 types) Set the I constant for 8 types.
"
□□□□
"
"
□□□□
"
to
"

"
I constant (PID control)
1 to 9999 [sec]
Use the [
], [
] and [ENT] keys to set the I constant for 8 types.
Use the [>] key to move the cursor to the right digit.
Set the numbers for 8 types at "Group No. (MODE3)".

□□□

SEL
SEL
D (8 types) Sets the D constant for 8 types.
"
□□□□
"
Function OFF
"
□□□□
"
to
"

"
D constant (PID control)
1 to 9999 [sec]
Use the [
], [
] and [ENT] keys to set the D constant for 8 types.
Use the [>] key to move the cursor to the right digit.
Sets the numbers for 8 types at "Group No. (MODE3)".

□□□

SEL
SEL
Output
Output limiter lower limit
(8 types)
Sets the lower limit of output limiter for 8 types.
"
□□

"
to
"

"
-5.0 to 100.0 [%]
Use the [
], [
] and [ENT] keys to set the output limiter lower limit for 8 types.
Use the [>] key to move the cursor to the right digit.
Set the numbers for 8 types at "Group No. (MODE3)".


SEL
SEL
Output limiter higher
limit (8 types)
Sets the higher limit of output limiter for 8 types.
"
□□□

"
to
"

"
0.0 to 105.0 [%]
Use the [
], [
] and [ENT] keys to set the output limiter higher limit for 8 types.
Use the [>] key to move the cursor to the right digit.
Set the numbers for 8 types at "Group No. (MODE3)".

□□□

SEL
SEL
Deviation
Guaranty soak (8 types)
[Program operation]
Sets the guaranty soak for 8 types.
"
□□□

"
Function OFF
"
□□□

"
to
"

"
0.1 to 3000.0 [%]
This display is available for the specification with program function.
The display appears when program operation is selected for "Program/constant
value operation switch (MODE2)".
Use the [
], [
] and [ENT] keys to set the guaranty soak for 8 types.
Use the [>] key to move the cursor to the right digit.
The decimal point position follows the SV decimal point position.
For detail description, refer to "5-5-3. Setting 8 parameters for each group
Setting
guaranty soak
Set the numbers for 8 types at "Group No. (MODE3)".