3 System Sengs
3.1 Sengs Overview
The SETTINGS MENU (Image 3.1.1) allows the user to adjust the system sengs (Table 3.1.1) and perform system level
acons such as a factory reset of the system sengs or clearing the data logs.
Image 3.1.1 · SETTINGS MENU
Select SETTINGS
MENU
Table 3.1.1 · SETTINGS MENU system sengs
MENU ITEM DESCRIPTION
BMS MODULE
The BMS MODULE menu allows the user to adjust the ming parameters for the ignion
sequence, whether the system is in AUTOMATIC or MANUAL mode, if PILOT ON DEMAND is
enabled or disabled, and set the TEMP LIMIT for the high temperature lockout.
PROCESS 1
There are four PROCESS menus, one for each process: 1, 2, 3, and INDEPENDENT. Each process
has the sengs: SOURCE, LOGIC, HIGH LEVEL, LOW LEVEL, CEILING and FLOOR.
PROCESS 2
PROCESS 3
PROCESS IND
PID
The PID menu has six sengs: SOURCE, SETPOINT, P VALUE, I VALUE, D VALUE, and DEADBAND
VALUE. The control output of the PID controller is the oponal ARControl 4-20 mA module.
SHUTDOWN 1
There are three SHUTDOWN menus, one for each shutdown: 1, 2, and 3. Each shutdown has the
sengs: SOURCE, LOGIC, HIGH LEVEL, and LOW LEVEL.
SHUTDOWN 2
SHUTDOWN 3
VALVE TIMING
The four valve outputs (Main Valve, Pilot Valve, Valve A, Valve B) have three sengs each:
DEADTIME, DELAY, and DUTY.
BATTERY LVD
The BATTERY LVD menu has two sengs: OK LEVEL and LOW LEVEL. When the baery voltage
transions from above to at or below the LOW LEVEL seng the system enters the LOW BATTERY
state in which all processes except for the Independent process is stopped. The processes can
only be started again once the baery voltage transions from below to at or above the
OK LEVEL seng.
MODBUS RS485
The MODBUS RS485 menu has three sengs: ADDRESS, BAUDRATE, and WORD ORDER.
These sengs allow the system to communicate with most PLCs and other industrial
communicaon equipment.
DATALOG
The DATALOG menu has three sengs: CONTRACT HOUR, DOWNLOAD MODE, and LOG
FREQUENCY. These sengs allow the customizaon of log frequency to meet customer or
regulatory requirements.
CALIB XDCR
The CALIB XDCR menu has four sengs: SPAN, ZERO, UNITS, and DECIMAL PLACE for transducer
calibraon. These sengs allow the system to accurately read dierent transducer topologies.
CALIB TC
The CALIB TC menu has three sengs: OFFSET TC1, OFFSET TC2, and UNITS for thermocouple
calibraon. These sengs allow for correcon of oset from the thermocouples. The UNITS
selecon allows exibility throughout internaonal regions.