3 System Sengs
3.1 Sengs Overview
The SETTINGS MENU (Image 3.1.1) allows the user to adjust the system sengs (Table 3.1.1) and perform system level
acons such as a factory reset of the system sengs or clearing the data logs.
Image 3.1.1 · SETTINGS MENU
Select SETTINGS
MENU
Table 3.1.1 · SETTINGS MENU system sengs
MENU ITEM DESCRIPTION
BMS MODULE
The BMS MODULE menu allows the user to adjust the ming parameters for the ignion
sequence, whether the system is in AUTOMATIC or MANUAL mode, if PILOT ON DEMAND is
enabled or disabled, and set the TEMP LIMIT for the high temperature lockout.
PROCESS 1
There are four PROCESS menus, one for each process: 1, 2, 3, and INDEPENDENT. Each process
has the sengs: SOURCE, LOGIC, HIGH LEVEL, LOW LEVEL, CEILING and FLOOR.
PROCESS 2
PROCESS 3
PROCESS IND
PID
The PID menu has six sengs: SOURCE, SETPOINT, P VALUE, I VALUE, D VALUE, and DEADBAND
VALUE. The control output of the PID controller is the oponal ARControl 4-20 mA module.
SHUTDOWN 1
There are three SHUTDOWN menus, one for each shutdown: 1, 2, and 3. Each shutdown has the
sengs: SOURCE, LOGIC, HIGH LEVEL, and LOW LEVEL.
SHUTDOWN 2
SHUTDOWN 3
VALVE TIMING
The four valve outputs (Main Valve, Pilot Valve, Valve A, Valve B) have three sengs each:
DEADTIME, DELAY, and DUTY.
BATTERY LVD
The BATTERY LVD menu has two sengs: OK LEVEL and LOW LEVEL. When the baery voltage
transions from above to at or below the LOW LEVEL seng the system enters the LOW BATTERY
state in which all processes except for the Independent process is stopped. The processes can
only be started again once the baery voltage transions from below to at or above the
OK LEVEL seng.
MODBUS RS485
The MODBUS RS485 menu has three sengs: ADDRESS, BAUDRATE, and WORD ORDER.
These sengs allow the system to communicate with most PLCs and other industrial
communicaon equipment.
DATALOG
The DATALOG menu has three sengs: CONTRACT HOUR, DOWNLOAD MODE, and LOG
FREQUENCY. These sengs allow the customizaon of log frequency to meet customer or
regulatory requirements.
CALIB XDCR
The CALIB XDCR menu has four sengs: SPAN, ZERO, UNITS, and DECIMAL PLACE for transducer
calibraon. These sengs allow the system to accurately read dierent transducer topologies.
CALIB TC
The CALIB TC menu has three sengs: OFFSET TC1, OFFSET TC2, and UNITS for thermocouple
calibraon. These sengs allow for correcon of oset from the thermocouples. The UNITS
selecon allows exibility throughout internaonal regions.