Failure to comply with the following safety warning(s) may result in serious personal injury or death.
Do not service the unit in a hazardous area
Contact Cimarron Energy, Inc. for informaon in regard to maintenance, parts, or service at 1-844-746-1676 or visit
www.cimarronenergy.com
PROBLEM SOLUTION
System will not exit Permissive open
alarm state
Verify Permissive input is closed circuit or jumped short.
System will not ignite
• Verify the address is set to DIP switch posion 1 on the BMS Module.
• Verify power and communicaon to the ignion module.
• Verify proper spark gap and ignion cable and grounding connecons.
• Inspect MODULE PORT fuse on the ARControl main board. Replace if
required.
System will not detect ame
• Verify proper placement of the ignion rod spark gap in the pilot ame.
• Verify proper ignion cable installaon and ground connuity.
System is in low baery mode too oen
• Verify the solar panel is posioned facing southward without any
obstrucons from the Sun.
• Verify the baery and solar panel are sized properly to handle the
system power requirements.
• Verify the gauge of wire used for the baery and solar panel are sized
properly to handle the system power requirements.
Pilot Status, Independent Process Valve,
Process 1 Valve, Process 2 Valve, Process
3 Valve, and Pilot Valve are not outpung
power.
Inspect the POWER PORT fuse on the ARControl main board. Replace if
required.
SPARE PARTS LIST
PART NUMBER DESCRIPTION
3181-002 ARControl 2 Amp Spare Fuse
1870-511 BMS Module - Black Ignion Module Puck
1960-170 BMS Module in Class I Division 1 Explosion Proof Enclosure
1960-171 BMS Module on DIN Rail Mounng Bracket
1960-160 5 Wa Solar Panel & 12 Volt 12 Amp Hour SLA Baery with Mounng Brackets
2130-012 12 Volt 12 Amp Hour SLA Baery
148197 12" Dual Probe Thermocouple - Type K for use with BMS Module
8100-020
0-5 psi millivolt pressure transducer with 1/4"-18 NPT male ng. Class I Division 2
when used with the ARControl BMS