88
7 Equipment Rangs
8 Approvals
Class I, Division 2, Groups C and D, T4A, Tamb. -40°C to +60°C, Type 4X
CAN/CSA-C22.2 NO. 61010-1:2012
CAN/CSA C22.2 NO. 213:2015
ANSI/ISA 12.12.01: 2015
UL 61010-1 (3rd Edion)
ANSI/ISA-61010-1
CAN/CSA-C22.2
UL 50E (Ed. 2)
PARAMETER MINIMUM TYPICAL MAXIMUM UNITS
Ambient Temperature -40 60 ˚C
Relave Humidity (Non-Condensing) 100 %
Enclosure Rang NEMA 4X
Operang Voltage 12 or 24 VDC
Operang Current 0.015 4 A
Solar Voltage 12 or 24 VDC
Solar Voltage 2 A
ALARM Output Voltage In 3 50 A
ALARM Output Current In 50 mA
All Valves Voltage Output 12 or 24 VDC
All Valves Current Output (Combined) 2 A
Thermocouple 1, 2, & TC BMS K
Permissive, Proof of Closure, PS2, & PS1 Input Voltage 5 30 VDC
BMS Module Valve Output Voltage 12 or 24 VDC
BMS Module Valve Output Current 2 A