WARNING!
1
1 Introducon
Thank you for purchasing the ARControl BMS Module, our most popular process control and ignion package.
This manual will provide you with important informaon that will help you understand the system, setup the system
and how the system operates. Please keep the manual in an accessible locaon for future reference. At Cimmaron
Energy Inc. we are always here to assist you with any service or spare part needs. Contact us at:
Phone: 1-844-746-1676
Website: hps://www.arcontrolbms.com
1.1 Hardware Installaon
The ARControl BMS should be installed according to the direcons provided in this manual and always be in compliance
with local electrical codes and the specicaons of the operang company. This secon will cover general instrucons
regarding safety as well as specic wiring and materials required for the safe and successful operaon of the ARControl
BMS.
1.1.1 Proper Use of the BMS Module 1870-511
The valve output on the BMS Module is the system’s ESD valve and is intended to be installed upstream of all other
valves in the ARControl BMS installaon. The dual-probe thermocouple input on the BMS Module is intended to be
used as the source for the high-temperature cuto. If the BMS Module 1870-511 is used in a manner not specied by
Cimarron Energy, Inc., the protecon provided by the equipment may be impaired.
Failure to comply with the following safety warning(s) may result in serious personal injury or death.
Ensure the power is not connected unl the nal step of installaon.
Failure of the grounding system integrity can result in personal injury, damage, or failure of operaon.
The equipment must be grounded in accordance with instrucons and devices and wiring connected to the
controller must be according to the appropriate electrical code
Ensure that no personnel nor any objects come into contact with the ignion module, terminals, or damaged
coil wiring. The ignion coil can generate 38kV and is considered a hazard.
If using an external power supply, do not power the ARControl with a supply rated for more than 24VDC.
Failure to comply with the following safety warning(s) may result in damage to the product.
When installaon is complete, ensure that the enclosure is properly sealed and the fasteners are ght. The
enclosure will ensure that the internal components are not aected by moisture, ice, or debris.
Disconnect and remove the baery during transportaon or when the ARControl will not be operated for
a period of me.
1.1.2 ARControl Installaon Guidelines
A switch or circuit breaker must be included in the installaon; it must be suitably located and easily reached. It
must be marked as the disconnecng device for the equipment.
Proper earth grounding per local electrical codes must be ulized in the installaon.
If the ARControl is used in a manner not specied by Cimarron Energy, Inc., the protecon provided by the
equipment may be impaired.
If the BMS Module (1870-511) is used in conjuncon with the ARControl it must be mounted externally of the
ARControl in order for the ARControl to remain regulatory compliant.
Use the hardware supplied with the ARControl. The hardware kit supplied with the ARControl contains an
aluminum pre-drilled mounng bracket, and (4) 3/4-inch bolts and nuts.
NOTICE