2
Locate the unit out of trac and working areas, away from excessive heat, and above areas where water and
liquids may accumulate. Visibility of the display will be enhanced if not facing direct sun.
Measure the wiring distance. The ignion cable is restricted to a length of 25 feet maximum.
1.1.3 ARControl BMS Installaon
Follow these steps to install the ARControl BMS (opons for DIN mount or CID1, temperature or pressure control):
WARNING: Do not apply power to the system unl instructed to do so in step 16. Failure to comply may result in
serious personal injury or death.
1. Locate and open the hardware kit.
2. Aach the mounng anges to the back of the ARControl (1960-155) with the supplied hardware.
3. Drill holes in the boom of the enclosure to accommodate the cables and conduit to the unit. It is recommended
to use a step drill bit to drill the holes.
4. Mount the ARControl via the anges to a secure locaon and away from heat sources.
5. Mount provided ignion rod assembly to the pilot or burner assembly.
6. When installing the BMS Module with included DIN bracket (1960-171) inside of the ARControl:
a. Aach provided cable conduit using provided glands to enclosure and burner chamber.
b. Mount the ignion module to the DIN rail on the inside of the enclosure. WARNING: Mounng ignion
module inside enclosure VOIDS the 1960-155 ARControl Class I Division 2 rang.
c. Wire the ignion module to the ARControl’s MODULE PORT using the provided wiring harness.
7. When installing the BMS Module with Class 1 Division 1 enclosure (1960-170) external from the ARControl:
a. Mount the BMS Module enclosure near the burner of the process equipment.
b. Aach suitable cable conduit between the ARControl and BMS Module.
c. Aach suitable cable conduit between the BMS Module and burner chamber.
d. Wire the ignion module to the ARControl’s MODULE PORT using suitable 4-conductor cable (Image 1.1.1).
8. Connect the ignion wire to the tab of the BMS Module spark transformer, run it through the conduit and
aach it to ignion rod assembly.
9. Aach the free end of the grounding wire (green wire with yellow trace) to the burners chassis.
10. Install dual-probe thermocouple (148197) in process equipment or combustor stack.
11. Wire dual-probe thermocouple to the BMS Module’s thermocouple ports using k-type thermocouple
extension wire.
12. If using Pressure Control (old SAU funconality), install 0-5 psig transducer (8100-020) in the process gas stream
and wire the transducer to the ARControl Transducer Port (Image 1.1.1).
13. Install the ESD valve upstream of the pilot and process valves and wire the ESD valve to the VALVE output of the
BMS Module.
14. Install the pilot valve upstream of the pilot and wire the pilot valve to the Pilot Valve output of the ARControl.
15. Install the process 1 valve upstream of the burner and wire the process 1 valve to the Process 1 Valve output of
the ARControl.
16. Connect the power source to the power and ground terminal blocks.
17. If using Pressure Control (old SAU funconality w/ Barksdale 8100-020), navigate to SETTING MENU >
PROCESS 1 and set the following:
SOURCE to XDCR
LOGIC to ↑ ON ↓ OFF
HIGH LEVEL to 50
LOW LEVEL to 20