The following are seng descripons, sengs opons and default values for the BMS MODULE sengs (Table 3.4.1).
Table 3.4.1 · BMS MODULE seng descripons, opons and default values
SETTING DESCRIPTION OPTIONS DEFAULT
MODE
Chooses between AUTOMATIC and MANUAL mode
operaon
Mode
AUTOMATIC
AUTOMATIC
MANUAL
PREPURGE TIME Duraon of the pre-purge period in seconds
Range Value
5Min 0
Max 600
IGNITION TIME Duraon of the ignion period in seconds
Range Value
30Min 1
Max 60
PURGE TIME
Duraon of the purge period between ignion
periods within the same cycle in seconds
Range Value
10Min 0
Max 10
WAIT TIME Duraon of the wait period in seconds
Range Value
0Min 0
Max 1800
IGNITION RETRY Number of ignion aempt retries
Range Value
2Min 0
Max 3
WAIT RETRY Number of wait period retries
Range Value
2Min 0
Max 3
PILOT EST TIME
Length of me required that pilot ame is to be
connuously detected before transioning to the
PILOT ON state.
Range Value
3Min 0
Max 3
ONDEMAND
Enables or disables the pilot on demand funconality
(only available in AUTOMATIC mode).
Mode
DISABLED
ENABLED
DISABLED
TEMP LIMIT
Temperature limit of the BMS dual channel
thermocouple that triggers a high temperature
lockout
Range °F °C
1600
Min 100 38
Max 2460 1348