C O M M I T S E T T I N G S
S O U R C Ø >
L O G I C < F O F >
H I G H L 0 0 0 0 1 >
E
O N
L = < +
0
= < +
= <
=
E E
V
L O W L L 0 0 0 0 > E V E
37
SHUTDOWN sengs (Image 3.4.16) include: SOURCE, LOGIC, HIGH LEVEL, and LOW LEVEL.
The following are seng descripons, sengs opons and default values for each SHUTDOWN seng (Table 3.4.4).
Image 3.4.16 · SHUTDOWN sengs
Table 3.4.4 · SHUTDOWN seng descripons, opons and default values
SETTING DESCRIPTION
OPTIONS
DEFAULT
SOURCE
Sets the input used as the shutdown
process variable.
Note: For PS1 and PS2 values see IO
Sengs
Mode Shutdown Default
Ø (NONE) 1 TC1
TC1 2 Ø (NONE)
TC2 3 Ø (NONE)
TC BMS
XDCR
PS1
PS2
LOGIC
Selects the logic applied to the high and
low levels and the output of the process
Mode Shutdown Default
↑ OFF ↓ ON 1 ↑ ON ↓ OFF
↑ ON ↓ OFF 2 ↑ ON ↓ OFF
WINDOW 3 ↑ ON ↓ OFF
INV WINDOW
HIGH LEVEL
Selects the shutdown upper threshold
value
Range Value Shutdown Default
Min -32768 1 1
Max 32767 2 1
3 1
LOW LEVEL
Selects the shutdown lower threshold
value
Range Value Shutdown Default
Min -32768 1 0
Max 32767 2 0
3 0