The following are seng descripons, sengs opons and default values for the VALVE TIMING sengs (Table 3.4.5).
Table 3.4.5 · VALVE TIMING seng descripons, opons and default values
SETTING DESCRIPTION
OPTIONS
DEFAULT
PRC 1 DEADTIME
Minimum amount of me in seconds that the valve
output must be either acve or inacve before it may
toggle again
Range Value
5Min 0
Max 10
PRCS 1 DUTY Duty cycle in % for the valve’s PWM operaon
Range Value
25Min 25
Max 100
PRC 2 DEADTIME Same as PRC 1 DEADTIME Same as PRC 1 DEADTIME 5
PRCS 2 DUTY Duty cycle in % for the valve’s PWM operaon Same as PRCS 1 DUTY 25
PRC 3 DEADTIME Same as PRC 1 DEADTIME
Range Value
5Min 0
Max 1000
PRCS 3 DUTY Duty cycle in % for the valve’s PWM operaon Same as PRCS 1 DUTY 25
PILOT DUTY Duty cycle in % for the valve’s PWM operaon Same as PRCS 1 DUTY 25
BMS DUTY Duty cycle in % for the valve’s PWM operaon Same as PRCS 1 DUTY 25
PRCS IND DUTY Duty cycle in % for the valve’s PWM operaon Same as PRCS 1 DUTY 25
PRCS IND DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Range Value
100Min 0
Max 1000
PRCS 1 DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Same as PRCS IND DELAY 100
PILOT DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Same as PRCS IND DELAY 100
PRCS 2 DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Same as PRCS IND DELAY 100
PRCS 3 DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Same as PRCS IND DELAY 100
BMS DELAY
Amount of me in milliseconds that the output is fully
on before the valve output starts PWM operaon
Same as PRCS IND DELAY 100