58
CVM-C4
Instruction Manual
Table 25 (Continued): Modbus Memory Map: Relay Outputs�
Relay outputs
Variable Format Address Valid data range
Relay 1 connection delay int 821
00,00 ... 99.99 s
Relay 2 connection delay int 829
(1)
If 00.00 is programmed, the relay is activated when the alarm is triggered and is deactivated when the alarm is
deactivated.
7.3.5.4. System conguration
Table 26: Modbus Memory Map: System conguration
System conguration
Variable Format Address Valid data range
Energy accumulation mode int 801
0: 4q, The active and reactive energy accumulate in
consumption and generation
1: 2t, The active and reactive energy accumulate in
consumption (positive). Tariffs 1 and 2 are displayed
for each of them.
Cyclic display
int 802
Byte 1:
0: Cyclic display activated; the display screen chang-
es every 3 s.
1: Cyclic display deactivated.
Light alarm
Byte 0:
1... 180%
(2)
Initial display screen
int 803
Byte 1:
0: Voltage - 1: Current - 2: Frequency,
3: Power - 4: Power factor
5: Energy - 6: THD
Backlight
Byte 0:
0... 255 s
(3)
(2)
If the value 0is programmed, the light alarm will be deactivated.
(3)
If the value 0is programmed, the display backlight is not turned off.
7�3�5�5� Deleting energy parameters
The energy parameters are deleted using Función 0x0E.
The deletion frame is:
Address Function
Relay
address
Password
Reset
Outputs
Value CRC
Address
Modbus
0E AACC 1111 01 FF xxxx