58
CVM-C4
Instruction Manual
Table 25 (Continued): Modbus Memory Map: Relay Outputs�
Relay outputs
Variable Format Address Valid data range
Relay 1 connection delay int 821
00,00 ... 99.99 s
Relay 2 connection delay int 829
(1)
If 00.00 is programmed, the relay is activated when the alarm is triggered and is deactivated when the alarm is
deactivated.
7.3.5.4. System conguration
Table 26: Modbus Memory Map: System conguration
System conguration
Variable Format Address Valid data range
Energy accumulation mode int 801
0: 4q, The active and reactive energy accumulate in
consumption and generation
1: 2t, The active and reactive energy accumulate in
consumption (positive). Tariffs 1 and 2 are displayed
for each of them.
Cyclic display
int 802
Byte 1:
0: Cyclic display activated; the display screen chang-
es every 3 s.
1: Cyclic display deactivated.
Light alarm
Byte 0:
1... 180%
(2)
Initial display screen
int 803
Byte 1:
0: Voltage - 1: Current - 2: Frequency,
3: Power - 4: Power factor
5: Energy - 6: THD
Backlight
Byte 0:
0... 255 s
(3)
(2)
If the value 0is programmed, the light alarm will be deactivated.
(3)
If the value 0is programmed, the display backlight is not turned off.
7�3�5�5� Deleting energy parameters
The energy parameters are deleted using Función 0x0E.
The deletion frame is:
Address Function
Relay
address
Password
Reset
Outputs
Value CRC
Address
Modbus
0E AACC 1111 01 FF xxxx