----- Supply network analyzer CVMk and CVMk-ITF ------ Page Nº 42
11.2.2. PROGRAMMING COMMANDS
COM-
MAND
CONCEPT QUESTION ANSWER
RRT
Read transforming ratios
(prim V, sec V, prim A)
$pp RRT ch
$pp 14 digits ch
(6 + 3 + 5 )
WRT
Write transforming ratios
$pp 14 digits ch
(6 + 3 + 5)
$PP ACK ch
RRS
Read communications (*)
$pp RRS ch
$pp 13 digits ch
WRS
Write communications (*)
$pp 13 digits ch
$PP ACK ch
RCP
Read configuration
Page 2 + Page3 + initial page
$pp RCP ch
$pp 13 digits ch
( 6 x 2 + 1 initial )
WCP
Write configuration. Page
$pp 13 digits ch
$PP ACK ch
RMM
Read type of set voltage
(single / compound)
$pp RMM ch
$PP 1 digit ch
1=S / 0 =C
WMM
Write measuring mode
(single / compound)
$pp 1 digit ch
1=single / 0 = comp
$PP ACK ch
VER
Read CVMk version
$pp VER ch
$PP 4 digits ch
TAR
Read type of card (module)
+ scale kW- MW (Lo - Hi )
$pp TAR ch
$PP 5 digits ch
( 4 card + 1 scale )
DEF
Write default parameters
$pp DEF ch
$PP ACK ch
INI
Reset
$pp INI ch
-------
(*) NOTE : The RRS / WRS command (communications):
- 2 digits peripheral number / 1 digit Parity / 1 digit length / 1 digit Stop bits/
4 digits Baud rate SERIAL output / 4 digit Baud rate 2nd output (only for "RED"
module: 2nd RS-485 output).