----- Supply network analyzer CVMk and CVMk-ITF  ------   Page  Nº  63
 MODBUS SELECTION
There are two ways for the change of the protocol  (CIRBUS or MODBUS ) :
a.- It is possible to access to a second MENU of SET-UP that allows the
configuration of the CVMk :   CIRBUS or MODBUS
(*) see the APPENDIX B.
b.- With  instructions via RS.
b.1.- When the device is on CIRBUS , for changing to MODBUS via RS, it is
done sending the command MBS.
CIRBUS -> MODBUS $PPMBSch ( Lf )  ASCII
PP  Peripheral number ( CVMk )
MBS Instruction to change from CIRBUS to MODBUS
ch CHECK SUM
b.2.- When the device is on MODBUS , for changing to CIRBUS via RS, it is
necesary to use the FUNCTION  6  ( Writing of 1 Word ) .
MODBUS -> CIRBUS PP0600000000CCCC BINARY
PP  Peripheral number ( CVMk )
06  Writing function  (Only  to change).
0000 Writing of 1 Word
0000 Writing register  : 0
  CCCC  CRC