118
SVGm
Instruction Manual
ENGLISH
 2.- PRODUCT DESCRIPTION
The SVG static var generator can be used to correct the power factor. For both backward (inductive) 
and forward (capacitive) currents.
The device features:
- 3/4-wire multifunction (depending on model), for installation in three-phase mains with or 
without neutral.
  - Parallel installation of up to 100 devices, depending on model.
 - EMI filters.
 - LCD touch display, to view the parameters.
 - RS-485 and Ethernet communications.
 - Enclosure type Rack, Cabinet o Wall (depending on model).
There are different models of the device, for different powers:
SVGm 20.7 and 30 kvar,
 
Table 3: Relation of models SVGm of 20.7 and 30 kvar.
Model
3 Wires 
( L1, L2, L3)  
4 Wires 
( L1, L2, L3, N) 
Type
Power
(kvar)
Mains voltage
(Un)
Maximum 
Parallelization
SVGm-4WF-020M-400 -
Wall 20.7  208 ... 400 V 100 units
SVGm-3WF-030M-480
- Wall 30  208 ... 480 V 100 units
 SVGm 41.4 and 60 kvar,
 
  
Table 4: Relation of models SVGm of 41.4 and 60 kvar.
Model
3 Wires 
( L1, L2, L3)  
4 Wires 
( L1, L2, L3, N) 
Type
Power
(kvar)
Mains voltage
(Un)
Maximum 
Parallelization
SVGm-4WF-040M-400 -
Wall 41.4 208 ... 400 V 100 units
SVGm-3WF-060M-480
- Wall 60 208 ... 480 V 100 units