171
Instruction Manual
SVGm
ENGLISH
Press the key to access the main screen of the device without saving the configuration values.
7.4.- OPERATING LIMITS
Note: This screen is not visible on the “slave” devices.
In this screen, Figure 62, the operating limits of the device are configured:
Figure 62: Configuration screen: Operating limits.
● Min current
The minimum load current to start the static generator is configured with this parameter. Minimum
current feature is used to increase the system efficiency, by stopping the static generator when re-
quired. The SVGm will stop when the load current is below the entered value and will start when it is
higher.
Table 26:Configuration values: Min current.
Min current
Minimum value 0 A
Maximum value 5000 A
● Current limit
This parameter allows the maximum power of the static generator to be limited. The value is config-
ured as a percentage with respect to the device’s rated power.
Table 27:Configuration values: Current limit.
Current limit
Minimum value 20 %
Maximum value 100 %
Press the key to access the next configuration step
Press the key to access the main screen of the device without saving the configuration values.