178
SVGm
Instruction Manual
ENGLISH
7.11.- TIME PROGRAMMER
Note: This screen is not visible on the “slave” devices.
Note: Feature available from HMI version 1.20 of the device.
A different configuration can be set up for the compensation mode in certain time slots, Figure 69.
Figure 69: Configuration screen: Time Programmer.
Enable the Enable ☑ option to let the device change compensation modes based on a schedule. Out-
side the schedule programmed in this section, the device compensates as per the mode programmed
in section “7.5 - cos Φ” and “7.6 - REACTIVE POWER OFFSET”.
Select the type of scheduling from the drop-down menu:
● Option P6 Spain, the schedule is preset as per time-of-use period P6.
● Option Custom, lets you set a different time band for every day of the week.
Note: If the start time is after the end time, the alternative program is activated between 00:00 and the
end time, and between the start time and 24:00.
Press the key to access the next configuration step
Press the key to access the main screen of the device without saving the configuration values.
7.12.- TIME PROGRAMMER: cos Φ
Note: This screen is not visible on the “slave” devices.
Note: Feature available from HMI version 1.20 of the device.
Note: Screen visible if Time Programmer option selected (“7.11 – TIME PROGRAMMER”).
In this section, the user selects the reactive power compensation mode that will be activated in the
time bands scheduled in section “7.11 - TIME PROGRAMMER “, Figure 70.