EasyManua.ls Logo

Circutor SVGm-4WF-020M-400 - Reactive Power Offset

Circutor SVGm-4WF-020M-400
218 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
173
Instruction Manual
SVGm
ENGLISH
7.6.- REACTIVE POWER OFFSET
Note: This screen is not visible on the “slave” devices.
Note: Feature available from HMI version 1.20 of the device.
On this screen, a fixed offset can be programmed that is added to the reactive power value calculated
to achieve the cos Φ programmed in section 7.5.- cos Φ (Figure 64).
Figure 64: Configuration screen: Offset.
Example: The device calculates that to achieve a cos Φ = 1 it must generate 50 kvar capacitive. An
offset of 30 kvar inductive is programmed. It will thus generate 50-30 = 20 kvar capacitive.
The offset value can be capacitive or inductive.
Table 29: Configuration values: Offset.
Offset
Minimum value 0 kvar
Maximum value 10000 kvar
Low Vac
Note: Operating mode available with software versions DSP ≥ 1.61 and HDMI ≥ 1.2006.
Enable this mode to keep the device from stopping as long as the mains voltage remains at 50% of its
initial value. See “4.7 - LOW MAINS VOLTAGE”.
Fast Reactive
Note: Operating mode available with software versions DSP ≥ 1.61 and HDMI ≥ 1.2006.
Enable this mode to reduce the response time to half a network cycle (10 ms in 50 Hz mains, 8.3 ms
in 60 Hz mains). See “4.8 - FAST REACTIVE MODE”.
Press the key to access the next configuration step
Press the key to access the main screen of the device without saving the configuration values.

Table of Contents