145
Instruction Manual
SVGm
ENGLISH
3.8.2.- CONNECTING CABINETS
To connect multiple cabinets in parallel, follow these steps:
1.- Select the cabinet that is to contain the “master” device.
2.- Connect the “master” cabinet. The current transformers are only connected to the “master” cabinet.
3.- Connect the “slave” cabinets.
4.- Connect all of the devices using the communication cables (Table 14).
Connect the OUT terminal from the final slave device in the “master” cabinet to the IN terminal from
the “master” device of the following cabinet, and the OUT terminal from the final “slave” device in this
cabinet to the IN terminal of the “master” device of the following cabinet, and so on (Figure 31).
Master Slave Slave
(*)
Connections already included in the cabinets
IN
OUT
2
3
2
3
IN
OUT
2
3
2
3
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
SVGm-xxx-200C
(*)
(*)
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
(*)
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
Figure 31: Connecting 3 devices in parallel, using the communication cable (200 kvar Master SVGm).
5.- Configure the installation in the “master” device (see “7. CONFIGURATION”.
6.- Complete the configuration of the slave devices (see “7.- CONFIGURATION”).
7.- Enable the terminator switch for parallel connection, RBUS (Terminal No 2 of Table 16) in the bus
end devices only. Then disable in the other devices.
Note: The 200 kvar (SVGm-3WF-200C), 300 kvar (SVGm-3WF-300C) and 400 kvar (SVGm-3WF-
400C) cabinets are made up of 2, 3 and 4 100 kvar devices in parallel.
The 138 kvar (SVGm-4WF-138C), 207 kvar (SVGm-4WF-207C) and 276 kvar (SVGm-4WF-276C) cab-
inets are made up of 2, 3 and 4 69 kvar devices in parallel.
The 134 kvar (SVGm-4WF-134C), 201 kvar (SVGm-4WF-201C) and 268 kvar (SVGm-4WF-268C) cabi-
nets are made up of 2, 3 and 4 67 kvar devices in parallel.
Both the parallel configuration and connection are factory-set.