EasyManua.ls Logo

Circutor SVGm-4WF-020M-400 - 3.8.2. Connecting Cabinets

Circutor SVGm-4WF-020M-400
218 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
145
Instruction Manual
SVGm
ENGLISH
3.8.2.- CONNECTING CABINETS
To connect multiple cabinets in parallel, follow these steps:
1.- Select the cabinet that is to contain the “master device.
2.- Connect the “master cabinet. The current transformers are only connected to the “master cabinet.
3.- Connect the “slave cabinets.
4.- Connect all of the devices using the communication cables (Table 14).
Connect the OUT terminal from the final slave device in the “master cabinet to the IN terminal from
the “master device of the following cabinet, and the OUT terminal from the final “slave” device in this
cabinet to the IN terminal of the “master device of the following cabinet, and so on (Figure 31).
Master Slave Slave
(*)
Connections already included in the cabinets
IN
OUT
2
3
2
3
IN
OUT
2
3
2
3
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
SVGm-xxx-200C
(*)
(*)
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
(*)
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
ON
RBUS
Figure 31: Connecting 3 devices in parallel, using the communication cable (200 kvar Master SVGm).
5.- Configure the installation in the “master device (see 7. CONFIGURATION”.
6.- Complete the configuration of the slave devices (see “7.- CONFIGURATION).
7.- Enable the terminator switch for parallel connection, RBUS (Terminal No 2 of Table 16) in the bus
end devices only. Then disable in the other devices.
Note: The 200 kvar (SVGm-3WF-200C), 300 kvar (SVGm-3WF-300C) and 400 kvar (SVGm-3WF-
400C) cabinets are made up of 2, 3 and 4 100 kvar devices in parallel.
The 138 kvar (SVGm-4WF-138C), 207 kvar (SVGm-4WF-207C) and 276 kvar (SVGm-4WF-276C) cab-
inets are made up of 2, 3 and 4 69 kvar devices in parallel.
The 134 kvar (SVGm-4WF-134C), 201 kvar (SVGm-4WF-201C) and 268 kvar (SVGm-4WF-268C) cabi-
nets are made up of 2, 3 and 4 67 kvar devices in parallel.
Both the parallel configuration and connection are factory-set.

Table of Contents