Figure 70: Configuration screen: Time Programmer: cos Φ.
Select the Scheduling Mode from the drop-down menu:
● Mode 1
In this mode, cos Φ is set to a fixed value. The device will attempt to ensure that the reactive power on
the mains side corresponds to the specified cos Φ.
Table 32: Configuration values: Mode 1.
Mode 1 cos Φ Offset
Range of values 0.7 ... -0.7 0 ... 10000 kvar.
● Mode 2
In this mode, two limits are defined to form an acceptance range. The device will adjust the reactive
power on the mains side to keep cos Φ within the specified acceptance range.
This mode minimises the amount of power used by the device to compensate for reactive power, thus
reducing its energy consumption.
Table 33: Configuration values: Mode 2.
Mode 2 cos Φ Offset
Range of values 0.7 ... -0.7 0 ... 10000 kvar.
● Fixed Q
This way, the device generates a constant reactive power.
Table 34: Configuration values:Fxed Q.
Fixed Q
Minimum value 0 kvar
Maximum value 10000 kvar
● Off
If this mode is programmed, the device turns off during the scheduled time band.
Press the key to access the next configuration step