Instruction Manual
SVGm
ENGLISH
Table 23 (Cont.): Warnings messages.
Alarm and event messages
Acción
correctora
This alert may be associated with transients and noise in the power supply voltage, or with incorrect
mains frequency values. Check the configuration. Check the quality of the power supply voltage. If it
continues, contact the TAS.
Min temperature
Description Temperature below the minimum operating value
Corrective
action
Wait for the environmental conditions to meet the requirements. If the alarm continues, contact the
Technical Service.
Mains frequency limits
Description Main frequency out of the limits
Corrective
action
This alert may be associated with transients and noise in the power supply voltage, or with incorrect
mains frequency values. Check the configuration. Check the quality of the power supply voltage. If it
continues, contact the Technical Service.
Minimum current
Description Mains current below the programmed level.
Corrective
action
Check the configuration.
Maximum load
Description Device working at full load
Corrective
action
No action is necessary.
Low load Power Factor
Description
The power factor value measured is less than 0.7, which might indicate a connection error in the
measuring transformers, where the voltage phases do not correspond to the current phases.
Corrective
action
Confirm that the connections are correct.
Reverse power
Description The power value measured is negative (generated power), which might indicate that the transformers
have been connected inversely.
Corrective
action
Confirm that the connections are correct.
W0080
(2)
Descripción Other warnings.
Acción
correctora
Contact the TAS.
NTP time server failure
Description Date not synchronised with NTP server.
Corrective
action
Schedule mode is activated. The SVGm tries to connect to an NTP time server. Communication fails,
or it is out of sync. It may take some minutes to synchronize. Check Ethernet communications and
access to Internet.
Remote meter comms failure
Description SVGm is failing to communicate with remote meter.
Corrective
action
Check SVGm configuration. Check communications and remote meter configuration.
Slave in alarm
Description This is a fault in one or more slaves.
Corrective
action
The device does not stop and adjusts its operation to the number of available slaves. On the slave
device status screen,6.12.- SLAVE DEVICE STATUS you can view the status and alarms for each
static generator. If there is a communications error with any of the slaves, stop the devices and check
the communications wiring.