206
SVGm
Instruction Manual
ENGLISH
SVGm-3WF-300C-690
SVGm-4WF-201C-550
SVGm-3WF-400C-690
SVGm-4WF-268C-550
Rated insulation voltage Ui 690 V 690 V
Impulse withstand voltage Uimp 6kV, CAT III Class 1 6kV, CAT III Class 1
Rated current
SVGm-3WF-300C-690 SVGm-3WF-400C-690
252 A 336 A
SVGm-4WF-201C-550 SVGm-4WF-268C-550
210 A 280 A
Short-time withstand current Icw 3.5 kA 1 second 3.5 kA 1 second
Peak current Ipk 84 kA peak 84 kA peak
Rated conditional short-circuit current Icc 40 kA 40 kA
Simultaneity RDF 1 1
Maximum consumption
SVGm-3WF-300C-690 SVGm-3WF-400C-690
6600 W 8800 W
SVGm-4WF-201C-550 SVGm-4WF-268C-550
6000 W 8000 W
Maximum current
SVGm-3WF-300C-690 SVGm-3WF-400C-690
252 A RMS 336 A RMS
SVGm-4WF-201C-550 SVGm-4WF-268C-550
210 A RMS 280 A RMS
Maximum power
690V
SVGm-3WF-300C-690 SVGm-3WF-400C-690
300000 VA 400000 VA
550V
SVGm-4WF-201C-550 SVGm-4WF-268C-550
201000 VA 268000 VA
Current measurement
Type Transformer: 5/5A ... 5000/5A
Consumption 1.5 VA per transformer
SVGm specifications
Response time < 100 s
Cos ɸ programmable 0.7 inductive ... 1 ... 0.7 capacitive
Parallel connection
Up to 100 devices of different calibres
Connection of the transformers only in the Master device
Fuses
SVGm-3WF-030M and SVGm-4WF-020M
Quantity 2 per phase
Type BS88A1, 25A, 500Vac gG 80kA I
2
t 21kA
2
s
SVGm-3WF-060M and SVGm-4WF-040M
Quantity 4 per phase
Type BS88A1, 25A, 500Vac gG 80kA I
2
t 21kA
2
s
SVGm-3WF-100M, SVGm-4WF-069M, SVGm-3WF-100R, SVGm-4WF-069R, SVGm-3WF-075M ans SVGm-4WF-050M
Quantity 2 per phase
Type type BS88 100A, 500Vac, gG 80kA I
2
t 21kA
2
s
SVGm-3WF-100C-690 and SVGm-4WF-067C-550
Quantity 2 per phase
Type type BS88/A4 63A, 660/690Vac, gG 80kA I
2
t 23kA
2
s