GENERAL RISKS
Particular area Danger Modality Instructions
Heat exchanger coils Superficial wounds Contact Avoid incidental contacts.
Wear protective gloves.
Install coil protective grills (optional).
LP Safety Valves Wounds
Intoxication
Refrigerant gas exhaust
due to the intervention of
the safety cut-out.
Avoid to enter the dangerous zone.
Pipe in an appropriate way the safety
exhaust valves.
Wear appropriate clothes and gloves.
Area surrounding the
unit
Wounds
Intoxication
Serious burns
Death
Explosion due to a rise
in ambient temperature
(fire).
Never shut the compressors inlet/outlet
valves when the unit is off.
Area surrounding the
unit
Death by:
Serious burns
Intoxication
Fire due to short-circuit
or overheating of the
power supply cables
before the unit mains
switch.
Exact measurement of cables and safety
cut-outs of the connections to the power
supply line.
Unit internal part Burns Contact with
compressors and
discharge pipes
Avoid incidental contacts
Wear protective gloves
Unit internal part Wounds Contact with sharp
corners
Wear protective gloves
Inner dangerous area Death by:
Electrocution
Metal parts under
tension.
Put scrupulously to earth the metal parts
of the unit.
Inner dangerous area Death by:
Electrocution
Serious burns
Contact with parts under
tension which one can
reach only after having
removed the protective
panels.
Open the unit mains switch and lock it with
a padlock before removing the panels.
COOLANT SAFETY DIAGRAMS
01 Identifying elements for
the substance
Product name: forane 407C
N°SDS 01965/1
Supplier: ELF ATOCHEM ITALIA
Via G.Murat 17, 20159 Milano tel. 02/668111
Product name: forane 22
N°SDS 0005/7
Supplier: ELF ATOCHEM ITALIA
4 cours Michelet Cedex 42, 92091 Paris, France.
Tel: 00331 49.00.80.80
02 Information concerning
composition of
components
Chemical nature of the compound
Mixture based on:
* Forane 32(difluoromethane) (N° CAS: 75-10-5)
* Forane 125 (pentafluoroethan) (N° CAS: 354-33-6)
* Forane 134a (1.1.1.2 tetrafluoroethan) (N° CAS: 811-97-2)
Chemical nature of the compound
Mixture based on:
Chlorodifluoromethane halogenated hydrocarbon
N° CAS 75-45-6
EINECS 200-871-9
03 Identification of risk Greatest physical and chemical dangers:
Thermal decomposition in toxic and corrosive products
Effects on health: practically non-toxic
Greatest physical and chemical dangers:
Thermal decomposition in toxic and corrosive products
Specific dangers/EEC: Dangerous for the ozone layer.
04 First-aid measures General information:
Inhalation: Carry the victim into the open air. Resort to oxygen or
artificial respiration if necessary.
Contact with skin: Frostbite must be treated in the same way as
burns.
Contact with the eyes: Immediate rinsing in abundant water. If
irritation should continue, consult an ophthalmologist.
Instructions for the physician: Do not administer
catecolammine (due to the cardiac sensitisation provoked by the
product)
General information:
Inhalation: Carry the victim into the open air. Resort to oxygen or
artificial respiration if necessary.
Contact with skin: Frostbite must be treated in the same way as
burns.
Contact with the eyes: Immediate rinsing in abundant water. If
irritation should continue, consult an ophthalmologist.
05 Fire prevention measures Specific dangers: Thermal decomposition into toxic and
corrosive products. Hydrofluoric acid. Carbon oxides.
Specific means of intervention: Cool containers/cisterns with
jets of water. Prevent any sparks or flames.
Do NOT smoke.
Special protection systems for fire-fighting squads: Carry
breathing apparatus and wear protective clothing
Specific dangers: Thermal decomposition into toxic and
corrosive products. Hydrofluoric acid. Hydrochloric acid in
gaseous form. Phosgene Carbon monoxides (CO).
Specific means of intervention: Cool containers/cisterns with
jets of water. Prevent any sparks or flames.
Do NOT smoke.
Special protection systems for fire-fighting squads: Carry
breathing apparatus and wear protective clothing.
06 Measures to take in case
of accidental spillage
Individual precautions: Avoid contact with the skin, eyes and
inhalation of vapours. Use personal protection means.
In an enclosed space: ventilate or use breathing apparatus (risk
of anoxia). NO SMOKING ALLOWED
Environment protection precautions: limit waste into
environment with the greatest care.
Individual precautions: Avoid contact with the skin, eyes and
inhalation of vapours.
In an enclosed space: ventilate or use breathing apparatus (risk
of suffocation). NO SMOKING ALLOWED.
Remove all risk of sparks or flames.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET MSAN 91 and is the answer not in the manual?

CLIVET MSAN 91 Specifications

General IconGeneral
BrandCLIVET
ModelMSAN 91
CategoryHeat Pump
LanguageEnglish

Related product manuals