ECON-4, SW version 1.4 rev.1, ©ComAp – March 2016 Draft 53
ECON-4 Reference guide.pdf
PreOverSpeed RPM
Step: 1RPM %
Range: Nominal RPM – Overspeed RPM
When actual RPM reaches this value Gas Dose (throttle position) is immediately set to Idle Fuel value
or zero (closed position) according setting in setpoint PreOverSpReduct
PreOverSpReduct IDLE FUEL/CLOSE
Step: -
Range: IDLE FUEL – CLOSE
Value set to output GAS Dose when RPM reaches value in setpoint PreOverSpeed.