ECON-4 1.4.0 Global Guide
55
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] -
Default value - Force value NO
Step -
Comm object 12091 Related applications ALL
Setpoint visibility WinScope only
Description
In case the actual RPM differs from Requested RPM for more than RPM window [RPM], the Speed PID
constants fluently change from Speed int to Speed int w and from Speed der to Speed der w. The aim of the
RPM window is to change the speed of regulation (reaction) in case the actual RPM differs significantly from
Requested RPM.
RPM Window
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0-100 %
Default value 10% Force value NO
Step 1 %
Comm object 12092 Related applications ALL
Setpoint visibility WinScope only
Description
Integration part of the PID regulation loop in case the actual RPM differs from Requested RPM for more than
RPM window.
Speed int w
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0,0-100,0 %
Default value 0% Force value NO
Step 0.1 %
Comm object 12176 Related applications ALL
Setpoint visibility WinScope only
Description
Derivative part of the PID regulation loop in case the actual RPM differs from Requested RPM for more than
RPM window..
Speed der w