ECON-4 1.4.0 Global Guide
68
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 0 – 100.0 %
Default value 0% Force value NO
Step 1 %
Comm object 14406 Related applications ALL
Setpoint visibility WinScope only
Description
Amount of derivation when Load decreases
LAder-
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 1.01 – 10.00 %
Default value 10 Force value NO
Step 0.01 %
Comm object 14404 Related applications ALL
Setpoint visibility WinScope only
Description
Derivation curve definition – drop from + value. Initial value is divided by this number repeatedly once per
0.1s. So higher value means faster drop to zero.
LAder+recover
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 1.01 – 10.00 %
Default value 10 Force value NO
Step 0.01 %
Comm object 14407 Related applications ALL
Setpoint visibility WinScope only
Description
Derivation curve definition – drop from - value. Initial value is divided by this number repeatedly once per
0.1s. So higher value means faster drop to zero.
LAder-recover
6 back to List of setpoints