ECON-4 1.4.0 Global Guide
67
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 0 – 100.0 %
Default value 5% Force value NO
Step 0.1 %
Comm object 14402 Related applications ALL
Setpoint visibility WinScope only
Description
Limit on Load step in + direction, changes bellow this limit will not generate any derivation
LAder+limit
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 0 – 100.0 %
Default value 5% Force value NO
Step 0.1 %
Comm object 14405 Related applications ALL
Setpoint visibility WinScope only
Description
Limit on Load step in – direction, changes bellow this limit will not generate any derivation
LAder-limit
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4
ADVextension module
Range [units] 0 – 100.0 %
Default value 0% Force value NO
Step 1 %
Comm object 14403 Related applications ALL
Setpoint visibility WinScope only
Description
Amount of derivation when Load increases
LAder+
6 back to List of setpoints