ECON-4 1.4.0 Global Guide
66
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] ± 10 V
Default value 10.00 V Force value NO
Step 0.01 V
Comm object 14376 Related applications ALL
Setpoint visibility [[[Undefined variable Specific.WinScopeOnly]]]
Description
Together with Max Fuel value creates coordinates for second point of Speed/Fuel line. For detailed
description see see Speed governor function in parallel mode on page 38ECON-4 Global Guide
SGO HiLim
Note: Setpoint is active for unloaded engine.
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 10 - 1800 s
Default value 30 s Force value NO
Step 1 s
Comm object 14375 Related applications ALL
Setpoint visibility [[[Undefined variable Specific.WinScopeOnly]]]
Description
This defines ramp according SGOoffset is removed after parallel. For details see chapter Speed governor
function in network parallel mode see see Speed governor function in parallel mode on page 38 ECON-
4 Global Guide.
SGOoffsetRamp
Note: Setpoint is active for unloaded engine.
6 back to List of setpoints

Table of Contents

Other manuals for ComAp ECON-4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp ECON-4 and is the answer not in the manual?

ComAp ECON-4 Specifications

General IconGeneral
BrandComAp
ModelECON-4
CategoryController
LanguageEnglish

Related product manuals