InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
FUNCTION NAME 
(ALPHABETICAL 
ORDER) 
RELATED SETPOINTS, INPUTS AND 
OUTPUTS 
Variable 
connection of 
devices on CAN 
bus 
It is possible to select number and type 
of devices connected on CAN2 bus 
(MODEM: I-LB+ or OTHER: InteliVision, 
I-RD). CAN addresses 123 and 124 are 
always dedicated to connection of 
OTHER devices (e.g. InteliVision 5 
CAN). Using two setpoints dedicated to 
this function, it is possible to choose if 
addresses 122 and 125 are used for 
communication by OTHER devices or in 
MODEM mode (i.e. prepared for I-LB+ or 
IB-NT connection). 
CANAddrSwitch1 
CANAddrSwitch2 
Voltage 
protections 
mode Ph-N or 
Ph-Ph 
AA 
 
 
In the controller it is possible to select 
whether fixed protections are based on 
measured Ph-N voltage or on measured 
Ph-Ph voltage. For more information of 
fixed protections please refer to the 
separate chapter Protections and Alarm 
management. 
Controller automatically detects if phases 
measurement is connected in wrong 
sequence (note that the wrong sequence 
is not detected if the phases are just 
rotated, i.e. L2-L3-L1) 
7.2  Modes 
7.2.1  OFF mode 
All regulations are switched off.  
Switching to OFF mode causes opening of BTB regardless of the settings. 
7.2.2  MAN mode 
It  is  possible  to  close/open  BTB  manually  under  supervision  of  IM-NT  controller  (automatic 
synchronization is started if there are voltages on both sides). 
Pressing BTB ON/OFF button closes/opens BTB if it is allowed by 
  setpoints Process control:Synchro enable, Mains coupling, DeadBusClosing 
  binary input BTB DISABLE 
NOTE:  
It is possible to close BTB in MAN mode without voltage on bus left and bus right based on setting of 
DeadBusClosing setpoint. 
7.2.3  AUT mode  
Controller closes automatically BTB if