InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
12.2.14.17 Setpoint: ActCallAttempt
This setpoint is used to adjust the maximum number of consequent attempts
to perform an active data call. The next attempt is performed 120s after the
previous unsuccessful attempt.
12.2.14.18 Setpoint: Acall+SMS lang
The setpoint specifies in which language the active SMS and e-mail
messages are issued. Adjust the setpoint to the index of the required
language. The index can be obtained from the tab Languages in GenConfig.
Index 1 is always english.
12.2.15 Group: Date/Time
12.2.15.1 Setpoint: Time stamp act
DISABLED, CONDITION, ALWAYS [-]
The setpoint selects the Time stamp function mode.
The function is disabled.
While the binary input Time stamp act is active the Time
stamps records are recorded into the history log with
period adjusted by setpoint Time Stamp Per.
The Time stamps records are recorded into the history
log with period adjusted by setpoint Time Stamp Per all
the time while the controler is switched on.