12.2.14.17 Setpoint: ActCallAttempt
Group
Act. calls/SMS
Range [units]
1 .. 250 [-]
Related FW
3.0
Description
This setpoint is used to adjust the maximum number of consequent attempts
to perform an active data call. The next attempt is performed 120s after the
previous unsuccessful attempt.
12.2.14.18 Setpoint: Acall+SMS lang
Group
Act. calls/SMS
Range [units]
1 .. 7 [-]
Related FW
3.0
Description
The setpoint specifies in which language the active SMS and e-mail
messages are issued. Adjust the setpoint to the index of the required
language. The index can be obtained from the tab Languages in GenConfig.
Index 1 is always english.
12.2.15 Group: Date/Time
12.2.15.1 Setpoint: Time stamp act
Group
Date/Time
Range [units]
DISABLED, CONDITION, ALWAYS [-]
Related FW
3.0
Description
The setpoint selects the Time stamp function mode.
DISABLED
The function is disabled.
CONDITION
While the binary input Time stamp act is active the Time
stamps records are recorded into the history log with
period adjusted by setpoint Time Stamp Per.
ALWAYS
The Time stamps records are recorded into the history
log with period adjusted by setpoint Time Stamp Per all
the time while the controler is switched on.

Table of Contents

Other manuals for ComAp IM-NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IM-NT and is the answer not in the manual?

ComAp IM-NT Specifications

General IconGeneral
BrandComAp
ModelIM-NT
CategoryController
LanguageEnglish

Related product manuals