12.2.2 Group: Basic settings
12.2.2.1 Setpoint: VbL VT ratio
The setpoint is used to adjust the busL voltage transformers ratio.
NOTE:
Adjust the setpoint to the value of 1.00 if the busL voltage is connected
directly to the controller terminals, i.e. without transformers.
NOTE:
Example: if you have transformers with ratio 6000/100V adjust the setpoint to
the value of 60.00.
NOTE:
The range of the busL voltage inputs must be adjusted properly. See the
setpoint VbL InpRangeSel.
12.2.2.2 Setpoint: VbL InpRangeSel
This setpoint selects the range of the busL voltage terminals. The 120V
range is available only in IM-NTC hardware. The IM-NT has the range
adjusted fixedly to 277V regardless of this setpoint.
NOTE:
The 277V range is suitable for both European (230V) and American (277V)
measurement. The range 120V is intended for high-voltage applications
where voltage transformers with 100V secondary range are used or for
alternative American (120V) measurement.
12.2.2.3 Setpoint: BusR VT ratio