The setpoint is used to adjust the busR voltage transformers ratio. 
NOTE:  
Adjust the setpoint to the value of 1.00 if the busR voltage is connected 
directly to the controller terminals, i.e. without transformers.  
 
NOTE:  
Example: if you have transformers with ratio 6000/100V adjust the setpoint to 
the value of 60.00.  
 
NOTE:  
The range of the busR voltage inputs must be adjusted properly. See the 
setpoint VbR InpRangeSel.  
 
 
12.2.2.4  Setpoint: VbRInpRangeSel 
This setpoint selects the range of the busR voltage terminals. The 120V 
range is available only in IM-NTC hardware. The IM-NT has the range 
adjusted fixedly to 277V regardless of this setpoint. 
NOTE:  
The 277V range is suitable for both European (230V) and American (277V) 
measurement. The range 120V is intended for high-voltage applications 
where voltage transformers with 100V secondary range are used or for 
alternative American (120V) measurement.  
 
 
12.2.2.5  Setpoint: BusLNomV 
This setpoint is used to adjust the nominal mains voltage (phase to neutral). 
If you do not know the phase-neutral nominal voltage, you can adjust the