12.2.4  Group: ComProtSetting 
12.2.4.1  Setpoint: Horn Timeout 
OFF, 1s - 3600s, NO TIMEOUT [-] 
This setpoint adjusts time after which the Horn output is automatically 
deactivated although the alarms still haven't been reset. If the setpoint is 
adjusted to OFF the horn output is not activated at all, the NO TIMEOUT 
position means the horn output is not deactivated until the alarms are reset. 
 
12.2.4.2  Setpoint: BinInp delay 1 
This setpoint adjusts the delay #1 which can be assigned to an input 
configured as alarm input (protection). 
NOTE:  
Protections configured at a binary inputs can have either fixed 0.5s 
evaluation delay or there are three independent delay setpoints and one of 
them can be assigned to each particular binary input protection.  
 
 
12.2.4.3  Setpoint: BinInp delay 2 
This setpoint adjusts the delay #2 which can be assigned to an input 
configured as alarm input (protection). 
NOTE:  
Protections configured at a binary inputs can have either fixed 0.5s 
evaluation delay or there are three independent delay setpoints and one of 
them can be assigned to each particular binary input protection.