Communication Guide, ©ComAp March 2014 106
IGS-NT Communication Guide 03-2014.pdf
Hint:
Setpoints Stringlist type (e.g. Controller Mode) is read as string and adjusted as index of
string item in string list. e.g. Controller Mode:
Read value
[as string]
Write value [as
index]
OFF
0
MAN
1
SEM
2
AUT
3
TEST
4
Example 5 reading and writing other type
S
MS:
#5:accesscode r8235,w8296
110.2
read value 8235,
write 110.2 with decimal point
A
nswer:
#Gen-set name:OIIIOOIIO,ok
read value of 8235 (binary
value),
writing was ok
Note: 1. Writing of binary setpoint is not supported.
2. Writing of setpoint with decimal point is automatically converted to
appropriate number of decimal places.
Example 6 reading actual Alarm list
S
MS:
#5:accesscode a
read actual Alarm list
A
nswer:
#Gen-set name:AL=(!Wrn
PrimWater temp, !Wrn SecWater temp,
Batt volt)
Actual Alarm list contains