InteliMains 210 Global Guide
108
Frequency
Bus Right Voltage Vbr1 Bus Right voltage Ph1
Bus Right Voltage Vbr2 Bus Right voltage Ph2
Bus Right Voltage Vbr3 Bus Right voltage Ph3
Bus Right Voltage Vbr12 Bus Right voltage Ph12
Bus Right Voltage Vbr23 Bus Right voltage Ph23
Bus Right Voltage Vbr31 Bus Right voltage Ph31
Bus Left Frequency Brfrq Bus Left Frequency
Bus Left Voltage Vbl1 Bus Left voltage Ph1
Bus Left Voltage Vbl2 Bus Left voltage Ph2
Bus Left Voltage Vbl3 Bus Left voltage Ph3
Bus Left Voltage Vbl12 Bus Left voltage Ph12
Bus Left Voltage Vbl23 Bus Left voltage Ph23
Bus Left Voltage Vbl31 Bus Left voltage Ph31
Bus Left Current IL1 Bus Left current Ph1
Bus Left Current IL2 Bus Left current Ph2
Bus Left Current IL3 Bus Left current Ph3
Voltage Battery VBat Voltage of battery
Binary Inputs BIN Controller binary inputs
Binary Outputs BOUT Controller binary outputs
Running nominal
power
TRPN Nominal power of all running gen-sets
Available nominal
power
APN Available nominal power of all gen-sets
Controller Mode Mode Controller mode
Note: When some setpoint is changed, in history log is written its number of communication object.
Note: Some additional columns can be added due to actual controller configuration (modules, etc.).
5.4.12 Breaker control
The following power switches are controlled by the controller:
TheBus Tie breaker or contactor – BTB
It is possible to use either a motorized circuit breaker or contactor. Below is a list of available control outputs
that should fit all types of contactors or breakers. The following rules must be kept to when designing the wiring
of power switches:
The control outputs must be configured and wiring of the power switches must be provided in such a way,
that the controller has full control over the breakers – i.e. the controller can open and close the breaker at any
time.
The breaker must respond within max. 2 seconds to a close and open command. Special attention should be
paid to opening of motorized circuit breakers, as it could take more than 2 seconds on some types. In such
cases it is necessary to use an undervoltage coil for fast opening.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals