17
2.5.5 EM-BIO8-EFCP
Hybrid current input and binary input/output extension module.
One additional AC current (CT) measuring for
Earth Fault Current protection (EFCP)
Wide range of measured current - one input for
1A and 1 input for 5A
Up to 8 additional configurable binary inputs or
outputs
2.6 CAN modules
2.6.1 Inteli AIN8
The unit offers the user the flexibility to configure the unit to have 8 analog inputs.
Supported sensors:
Resistor 3-wire input
Common resistor: 0-250Ω, 0-2400Ω, 0-10kΩ
Temperature sensor: Pt100, Pt1000, Ni100,
Ni1000
Current (active or passive sensors)
±20mA , 0-20mA, 4-20mA
Voltage
±1V, 0-2,4V, 0-5V, 0-10V
Lambda probes
Thermocouples are not supported (the
measuring loop was designed for lambda
probes, what caused non-support of
thermocouples)
Impulse/RPM sensor:
RPM measuring pulses with frequency 4Hz
10kHz
Impulse
Possibility to measure pulses from
electrometer, flowmeter (measurement of
total consumption, average fuel
consumption)

Table of Contents

Related product manuals