InteliMains 210 Global Guide
185
Group: Bus Left Settings
Subgroup: Overload Protection
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0 .. 200 [%]
Default value 120 % Alternative config NO
Step
1 % of Nominal Bus Import (page 175)
Comm object 8280 Related applications MCB, MGCB, BTB
Description
Threshold level for Bus Left overload (in % of Nominal power) protection. Protection is BOR.
Overload BOR
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0 .. 200 [%]
Default value 120 % Alternative config NO
Step
1 % of Nominal Bus Import (page 175)
Comm object 9685 Related applications MCB, MGCB, BTB
Description
Threshold level for Bus Left overload (in % of Nominal power) protection. This is only warning.
Overload Wrn
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8281 Related applications MCB, MGCB, BTB
Description
Delay for Overload BOR (page 185) and Overload Wrn (page 185) protection.
Overload Delay
6 back to List of setpoints