InteliMains 210 Global Guide
184
Subgroup: Bus Right Frequency Limits
Setpoint group Bus Right Settings Related FW 2.0.0
Range [units]
Bus Right Underfrequency (page 184) .. 150 [%]
Default value 102,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 178)
Comm object 9688 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Right overfrequency.
Bus Right Overfrequency
6 back to List of setpoints
Setpoint group Bus Right Settings Related FW 2.0.0
Range [units]
50 .. Bus Right Overfrequency (page 184) [%]
Default value 98,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 178)
Comm object 9689 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Right underfrequency.
Bus Right Underfrequency
6 back to List of setpoints
Setpoint group Bus Right Settings Related FW 2.0.0
Range [units] 0,0 .. 60,0 [s]
Default value 0,5 s Alternative config NO
Step 0,1 s
Comm object 8297 Related applications MCB, MGCB, BTB
Description
Delay for Bus Right Underfrequency (page 184) and Bus Right Overfrequency (page 184) protection.
Bus Right < > Frequency Delay
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals