InteliMains 210 Global Guide
178
Subgroup: Frequency settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 8278 Related applications MCB, MGCB, BTB
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Frequency 1 (page
294), Nominal Frequency 2 (page 296) and Nominal Frequency 3 (page 298).
Nominal Frequency
6 back to List of setpoints
Subgroup: Controller settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] OFF / MAN / AUTO / TEST [-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications MCB, MGCB, BTB
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via MODBUS. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
Controller mode
6 back to List of setpoints