InteliMains 210 Global Guide
179
Setpoint group Basic settings Related FW 2.0.0
Range [units] Previous / OFF [-]
Default value Previous Alternative config NO
Step [-]
Comm object 13000 Related applications MCB, MGCB, BTB
Description
This setpoint adjusts controller mode after power on of controller.
Previous When controller is power on, than is switched into last mode before power off.
OFF When controller is power on, than is switched into OFF mode.
Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via LBI.
After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
Power On Mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 2.0.0
Range [units] Disabled / 1 .. 255 [min]
Default value Disabled Alternative config NO
Step 1 min
Comm object 10121 Related applications MCB, MGCB, BTB
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
Backlight Timeout
6 back to List of setpoints
Setpoint group Basic settings Related FW 2.0.0
Range [units] Disabled / 1 .. 599 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8264 Related applications MCB, MGCB, BTB
Description
Setting of horn behavior.
Disabled Disabling the Horn sounding function
1 .. 599 [s]
Timeout for HORN (PAGE 459) binary output. The HORN (PAGE 459) output is opened when
this timeout elapsed.
Note: Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
Horn Timeout
6 back to List of setpoints