180
Subgroup: Phase rotation
Setpoint group Basic settings Related FW 2.0.0
Range [units] Clockwise / CounterCCW [-]
Default value Clockwise Alternative config NO
Step [-]
Comm object 15122 Related applications MCB, MGCB, BTB
Description
This setpoint adjust the phase sequence of voltage terminals.
Phase Rotation
6 back to List of setpoints
Subgroup: Battery Protections
Setpoint group Engine settings Related FW 2.0.0
Range [units]
8,0 V .. Battery Overvoltage (page 180) [V]
Default value 18,0 V Alternative config NO
Step 0,1 V
Comm object 8387 Related applications MCB, MGCB, BTB
Description
Warning threshold for low battery voltage.
Battery Undervoltage
6 back to List of setpoints
Setpoint group Engine settings Related FW 2.0.0
Range [units]
Battery Undervoltage (page 180) .. 40,0 [V]
Default value 36,0 V Alternative config NO
Step 0,1 V
Comm object 9587 Related applications MCB, MGCB, BTB
Description
Warning threshold for high battery voltage.
Battery Overvoltage
6 back to List of setpoints