InteliMains 210 Global Guide
182
Setpoint group
Communication
Settings
Related FW 2.0.0
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 57600 bps Alternative config NO
Step [-]
Comm object 24135 Related applications MCB, MGCB, BTB
Description
If the direct mode is selected on on-board RS485, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.
Note: Winscope supports only 19200, 38400, 57600 speeds.
RS485 Communication Speed
6 back to List of setpoints
Setpoint group
Communication
Settings
Related FW 2.0.0
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Alternative config NO
Step [-]
Comm object 24141 Related applications MCB, MGCB, BTB
Description
If the MODBUS mode is selected on COM1 channel, the MODBUS communication speed can be adjusted
here.
RS485 MODBUS Speed
6 back to List of setpoints
Group: Bus Right Settings
Subgroup: Bus Right Voltage Limits
Setpoint group Bus Right Settings Related FW 2.0.0
Range [units]
Bus Right Undervoltage (page 183) .. 150 [%]
Default value 110 % Alternative config NO
Step
1 % of Nominal Voltage Ph-Ph (page 177)
Comm object 9686 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Right overvoltage. All three phases are checked. Maximum out of three is used.
Bus Right Overvoltage