InteliMains 210 Global Guide
156
Reading binary inputs as coil status.
Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses
Modbus Addr.
Prot. Addr.
Source
= Value
= State
C.O.#
State #
Name of Value
Name of State
Bit #
Bit Name
Activated by protection(s):
Group
00000 Value 8235 Binary Inputs 1 GCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 2 MCB Feedback Controller I/O
00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I/O
We will read state of MCB Feedback binary input.
Request: (Numbers in Hex)
01 01 00 01 00 01 AC 0A
Controller address Modbus function
Register address
0001
hex
= 0001
dec
Number of registers CRC
Response: (Numbers in Hex)
01 01 01 01 90 48
Controller address Modbus function
Length of data
01
hex
= 1 byte read
Data
01
hex
= active
CRC
The readed data is 01, it means this binary input is active.
Note: You can use modbus function 2 insted of 1, rest of data remains same (CRC differs).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals