EasyManua.ls Logo

ComAp InteliMains 210 BTB

ComAp InteliMains 210 BTB
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains 210 Global Guide
158
Password
This password is the same as in InteliConfig or directly in controller.
Table Reserved registers (page 151)
Register addresses Number of registers Access Data type Meaning
4211 1 write Unsigned16 Password
Note: Default password is "0".
In this example the password is "1234".
Request: (Numbers in Hex)
01 06 10 73 04 D2 7C D1
Controller address Modbus function
Register address
1073
hex
= 4211
dec
Password
04D2
hex
= 1234
dec
CRC
Response for success: (Numbers in Hex)
01 06 10 73 00 00 7C D1
Controller address Modbus function
Register address
1073
hex
= 4211
dec
Allways zero. CRC
Response for bad password: (Numbers in Hex)
01 86 04 43 A3
Controller
address
Modbus exception
for function 6.
04 device error
see Error codes (exception codes) on page 151
CRC

Table of Contents

Related product manuals