InteliMains 210 Global Guide
375
Value group Power Management Related FW 2.0.0
Units %
Comm object 10788 Related applications MCB, MGCB, BTB
Description
Actual relative reserve in power management.
Actual Relative Reserve
6 back to List of values
Value group Power Management Related FW 2.0.0
Units kW
Comm object 15806 Related applications MCB, MGCB, BTB
Description
Actual absolute reserve for start.
Start Reserve
6 back to List of values
Value group Power Management Related FW 2.0.0
Units kW
Comm object 15807 Related applications MCB, MGCB, BTB
Description
Actual absolute reserve - when the reserve is higher than this value the last started gen-set (the gen-set with
the highest priority) is stopped.
Stop Reserve
6 back to List of values
Value group Power Management Related FW 2.0.0
Units %
Comm object 10786 Related applications MCB, MGCB, BTB
Description
Actual relative reserve for start.
Start Relative Reserve
6 back to List of values
Value group Power Management Related FW 2.0.0
Units %
Comm object 10787 Related applications MCB, MGCB, BTB
Description
Actual relative reserve - when the relative reserve is higher than this value the last started gen-set (the gen-
set with the highest priority) is stopped.
Stop Relative Reserve
6 back to List of values