Maximum current 1.0 A
Maximum switching voltage 36 V DC
Horn output
Galvanic separated
Maximal CAN bus length 200 m
Speed 250 kBd
Nominal impedance 120 Ω
Cable type twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length
Nominal Velocity of Propagation min. 75 % (max. 4,4 ns/m)
Wire crosscut min.0,25 mm
2
Maximal attenuation (at 1 MHz) 2 dB/100m
Recommended Industrial Automation & Process Control Cables
BELDEN (www.belden.com)
3082A DeviceBus for Allen-Bradley DeviceNet
3083A DeviceBus for Allen-Bradley DeviceNet
3086A DeviceBus for Honeywell SDS
3087A DeviceBus for Honeywell SDS
3084A DeviceBus for Allen-Bradley DeviceNet
3085A DeviceBus for Allen-Bradley DeviceNet
3105A Paired EIA Industrial RS485 cable
LAPP CABLE (www.lappcable.com)
Unitronic BUS DeviceNet Trunk Cable
Unitronic BUS DeviceNet Drop Cable
Unitronic BUS CAN
Unitronic-FD BUS P CAN UL/CSA
CAN bus interface