Loading...
Technical Data
The device is intended to be used in the engine room or on the engine directly.
HW Modification
RS-485
isolated
Distance
[m]
Binary
Output
Analog
Input
Backlit
(Display
Buttons)
Protected
IP
Internal
buzzer
InteliVision 5
No 2 No No No IP-65
(face)
No
InteliVision 5
Remote
Display
Yes 1000 Yes Yes Yes IP-65
(face)
Yes
Power Supply
Value Controller IV5 Display
Voltage supply 8-36V DC 8-36V DC
Consumption depends on supply
voltage
1,1A at 8VDC 0,7A at 8 VDC
Hint:
InteliVision 5 should be use with the same battery as the control unit. When external battery is needed
because of long wiring and etc.. InteliVision 5 RD is recommended to use.
Operating Conditions
Operating temperature -40...+70
o
C
Storage temperature -30...+80
o
C
Flash memory data retention time 10 years
Protection front panel IP65
Humidity 85% without condensation
IEC/EN 60068-2-30
Standard Conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 61000-6-3
EN 61000-6-4
EN 61000-6-1
EN 61000-6-2
Vibration EN 60068-2-6
Dimensions and Weight
Dimensions Front panel 245x164mm
LCD display cutout 175x115mm
Weight 855g
InteliVision 5-1.1 Reference Guide ©ComAp – December 2011 41