Specifications C-7
Battery Runtime
Table C-9
Estimated Battery Runtime (Minutes)
Total Load (VA)
1000
Tower Models
1500
Tower Models
Rack-Mountable
Models
350 30 67 57
400 26 59 50
450 23 43 36
500 21 38 32
600 16 32 27
700 14 27 23
800 12 24 20
900 9 17 15
1000 8 16 13
1200 13 11
1400 10 8
1500 9 7
Note: Volts x Amps = VA per device. Add all device VAs for total load.
If a device lists the power in Watts, use the following conversion equation:
Watts x 1.35 = VA