19
rear exit horizontal termination
Simple venting configuration
See graph to determine the required vertical rise
V
T
for the required
1.6
(0.5)
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
T
The shaded area within the lines represents acceptable values for H
T
and H
T
For vent configurations requiring more than two 90° elbows, the following formulas apply:
+ V
2
= 9FT (2.7m) + 6FT (1.8m) = 15FT (4.6m)
= 3FT (0.9m) + 2FT (0.6m) + 1.5FT (0.5m) = 6.5FT (2m)
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
+ H
O
= 6.5FT (2m) + 8.1FT (2.5m) = 14.6FT (4.5m)
= 14.6FT (4.5m) + 15FT (4.6m) = 29.6 FT (9m)
14.6 FT (4.5m) < 15 FT (4.6m)
29.6 FT (9m) < 40 FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
W415-1679 / D / 03.09.18